Product Features

  • Valve Regulated Lead Acid (VRLA) Battery
  • Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
  • Pure Lead Construction and Proprietary Elements
  • Designed for High-Rate UPS, Float Service Standby Power Applications
  • Built in Accordance with IEC 61056-1/2:2012 and UL1989 Recognized (MH14533)

Application Scenarios

  • Data center UPS backup battery
  • Server room uninterruptible power supply
  • Industrial UPS high-power backup
  • Medical equipment UPS emergency power
  • Financial system UPS backup
  • Telecom room UPS backup

Product parameters

  • Model:UPS122406
  • Voltage:12 Vdc
  • Nominal Capacity:240W @5min-rate
  • Watts per Cell:38.83 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:18.5 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:2.00 A
  • Max. Discharge Current:130 A
  • Short Circuit Current:230 A
  • Internal Resistance:33.50 mΩ
  • Terminal Type:F2 terminal (Faston Tab 250)
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:1.46 / 3.22 kg / lb.
  • Length (L):150.9±2.0 / 5.94±0.08 mm / in
  • Width (W):51.0±1.0 / 2.01±0.04 mm / in
  • Height (H):98.6±1.0 / 3.88±0.04 mm / in
  • Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
  • Note:F1 terminal is available; Max Discharge Current = 100 A (5 sec.)

Product details

The CSB UPS122406 belongs to the UPS series, a 6V and 12V top terminal valve-regulated sealed lead-acid (VRLA) battery using absorbed glass mat (AGM) technology, with gas recombination efficiency up to 99%, maintenance-free. This series features pure lead construction, designed for high-rate discharge and float standby scenarios in uninterruptible power supplies (UPS), with official application areas being data center UPS. In terms of electrical parameters, the UPS122406 has a nominal voltage of 12 Vdc, nominal capacity measured at 9.60V per PCS @ 25°C, 240W @5min-rate. Its power per cell is 38.83 W/cell at 5 minutes 1.67 VPC @ 25°C, and 18.5 W/cell at 15 minutes 1.67 VPC @ 25°C. Maximum charge current is 2.00 A, maximum discharge current is 130 A, short-circuit current is 230 A, and internal resistance is 33.50 mΩ. Float charge voltage is 13.5 to 13.8 Vdc/battery (25°C), equalizing charge voltage is 14.4 to 15.0 Vdc/battery (25°C). The battery's terminal type is F2 terminal - Faston Tab 250. The case material is ABS (UL 94-HB), with a flame-retardant (94-V0) version available upon request. Dimensions are length 150.9±2.0 mm, width 51.0±1.0 mm, height 98.6±1.0 mm, weight approximately 1.46 kg. Design life is up to 5 years at 25°C float standby service, and 3 to 5 years per Eurobat (20°C) standard commercial. Operating temperature: nominal temperature is 25°C (77°F), discharge temperature is -15°C to 50°C (5°F to 122°F), charge and storage temperature is -15°C to 40°C (5°F to 104°F). In terms of self-discharge characteristics, self-discharge is less than 10% after 90 days storage at 25°C (77°F), can be stored for up to 6 months; fully charge before use, and if storage temperature is above 25°C (77°F), charge earlier. The product complies with IEC 61056-1/2:2012 standard and is recognized to UL1989 (MH14533). These features make it suitable for applications such as data center UPS requiring high-rate discharge and float standby.