Product Features

  • Valve Regulated Lead Acid (VRLA) Battery
  • Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
  • Pure Lead Construction and Proprietary Elements
  • Designed for High-Rate UPS, Float Service Standby Power Applications
  • Built in Accordance with IEC 61056-1/2:2012 and UL1989 Recognized (MH14533)

Application Scenarios

  • Small and medium data center UPS backup
  • Server rack uninterruptible power supply
  • Network room emergency power protection
  • Medical imaging equipment UPS backup
  • Industrial control UPS fast discharge
  • Laboratory precision instrument backup power

Product parameters

  • Model:HR12120W
  • Voltage:12 Vdc
  • Nominal Capacity:120W @15min-rate
  • Watts per Cell:232.17 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:123 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:12 A
  • Max. Discharge Current:225 A
  • Short Circuit Current:928 A
  • Internal Resistance:8.2 mΩ
  • Terminal Type:I1 thread lead alloy recessed terminal to accept M5 bolt
  • Terminal Torque:30.4±6.1 Kgf·cm / 26.4±5.3 Lbf·in / 3.0±0.6 N·m
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:10.2 / 20.48 kg / lb.
  • Length (L):166±2.0 / 6.54±0.08 mm / in
  • Width (W):125±1.5 / 4.92±0.06 mm / in
  • Height (H):175±2.0 / 6.89±0.08 mm / in
  • Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB HR12120W belongs to the HR series of high-rate discharge pure lead batteries. The product type is a 12V top terminal valve-regulated sealed lead-acid battery, and its official application area is data center uninterruptible power supplies. This series is positioned as a high-rate discharge pure lead battery series for smaller-output UPS and rapid-discharge standby scenarios. The battery adopts valve-regulated sealed lead-acid construction and absorbed glass mat technology, with gas recombination efficiency of up to 99%, is maintenance-free, and features pure lead construction and proprietary element design, making it suitable for high-rate UPS and float standby power applications. In terms of electrical parameters, the HR12120W has a voltage of 12 Vdc and a nominal capacity of 120W @15min-rate (1.67 VPC @25°C). Its 5-minute rate power is 232.17 W/cell, and its 15-minute rate power is 123 W/cell (both at 1.67 VPC @25°C). Maximum charge current is 12 A, maximum discharge current is 225 A, short-circuit current is 928 A, and internal resistance is 8.2 mΩ. Float charge voltage is 13.5 to 13.8 Vdc/battery (25°C), and equalizing charge voltage is 14.4 to 15.0 Vdc/battery (25°C). Mechanically, the battery terminal is I1-Thread lead alloy recessed terminal to accept M5 bolt, with terminal torque of 30.4±6.1 Kgf·cm, 26.4±5.3 Lbf·in, or 3.0±0.6 N·m. The case material is ABS (UL 94-HB), and a flame-retardant (94-V0) version is available upon request. Weight is 10.2 kg (20.48 lb), and dimensions are length 166±2.0 mm, width 125±1.5 mm, height 175±2.0 mm. Regarding operating temperature, the nominal temperature is 25°C, the discharge temperature range is -15°C to 50°C, and the charge and storage temperature range is -15°C to 40°C. Design life is up to 5 years in float standby service at 25°C, and 3 to 5 years per Eurobat (20°C) standard commercial. Self-discharge is less than 10% after 90 days, and the battery can be stored at 25°C for up to 6 months and requires a full charge before use; if storage temperature exceeds 25°C, it should be charged sooner. The product is manufactured in accordance with IEC 61056-1/2:2012 and is UL1989 Recognized (MH14533).