CSB XHRL12250W 12V Valve-Regulated Sealed Lead-Acid Battery
The CSB XHRL12250W is a 12V valve-regulated sealed lead-acid battery in the XHRL series, designed for high-rate standby power such as data center UPS. It delivers 250W at the 15-minute rate, 463.17 W/cell at the 5-minute rate, float charge voltage of 13.5-13.8 Vdc, and a design life of up to 10 years.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) Battery
- Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
- Pure Lead Construction and Proprietary Elements
- Designed for High-Rate UPS, Float Service Standby Power Applications
- Built in Accordance with IEC 60896-21/22:2004 and UL1989 Recognized (MH14533)
Application Scenarios
- Very large data center UPS backup
- High-performance computing center backup power
- Cloud computing data center UPS
- Financial data center uninterruptible power supply
- Telecom hub high-rate discharge backup
- Industrial-grade UPS high-power backup
Product parameters
- Model:XHRL12250W
- Voltage:12 Vdc
- Nominal Capacity:250W @15min-rate
- Watts per Cell:463.17 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:252.67 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:25.00 A
- Max. Discharge Current:650 A
- Short Circuit Current:1680 A
- Internal Resistance:4.20 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:18.52 / 40.82 kg / lb.
- Length (L):228.0±2.5 / 8.98±0.10 mm / in
- Width (W):138.4±1.5 / 5.45±0.06 mm / in
- Height (H):206.3±2.5 / 8.12±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB XHRL12250W is a 12V valve-regulated sealed lead-acid battery belonging to the XHRL series. This series is a high-performance variant of HRL, providing higher high-rate output for UPS and data center requirements. The battery uses absorbed glass mat (AGM) technology, with gas recombination efficiency up to 99%, a maintenance-free design, and pure lead construction with proprietary elements. Its official application area is data center uninterruptible power supplies, suitable for high-rate discharge and float standby scenarios.
In terms of electrical parameters, the XHRL12250W has a nominal voltage of 12 Vdc and a nominal capacity of 250W (1.67 VPC @25°C, 15-minute rate). The 5-minute rate power is 463.17 W/cell, and the 15-minute rate power is 252.67 W/cell (1.67 VPC @25°C). The maximum charge current is 25.00 A, the maximum discharge current is 650 A, the short-circuit current is 1680 A, and the internal resistance is 4.20 mΩ. The float charge voltage is 13.5 - 13.8 Vdc/battery (25°C), and the equalizing charge voltage is 14.4 - 15.0 Vdc/battery (25°C).
The battery's terminal type is I2 threaded lead alloy terminal, accepting M6 bolts, with a terminal torque of 51.7±10.3 Kgf∙cm or 44.9±9.0 Lbf∙in or 5.1±1.0 N∙m. The case material is PP (UL 94-HB), and a flame-retardant version (94-V0) is available upon request. The weight is 18.52 kg (40.82 lb), and the dimensions are length 228.0±2.5 mm, width 138.4±1.5 mm, height 206.3±2.5 mm.
In terms of design life, the XHRL12250W can reach 10 years in float standby service at 25°C, meeting the Eurobat standard (20°C) very long life classification of greater than 12 years. The operating temperature range is: nominal 25°C, discharge -15°C to 50°C, charge/storage -15°C to 40°C. The self-discharge rate is less than 10% after 90 days at 25°C, and it can be stored for up to 6 months, requiring a full charge before use; if the storage temperature is above 25°C, charge in advance.
This battery is manufactured according to IEC 60896-21/22:2004 and is recognized under UL1989 (MH14533). Its high-rate discharge characteristics make it suitable for data center UPS and other applications requiring reliable standby power, meeting the requirements of float service standby applications.