CSB HRL12200W 12V 200W VRLA Battery
The CSB HRL12200W is a 12V valve-regulated lead-acid battery with HRL series high-rate pure lead design, 200W at 15-minute rate, 385W/cell at 5-minute rate, suitable for data center UPS float standby power.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) Battery
- Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
- Pure Lead Construction and Proprietary Elements
- Designed for High-Rate UPS, Float Service Standby Power Applications
- Built in Accordance with IEC 60896-21/22:2004 and UL1989 Recognized (MH14533)
Application Scenarios
- Large data center UPS backup
- Cloud computing center HVDC backup
- Financial trading system UPS
- Telecom hub UPS emergency protection
- Industrial automation UPS high-power backup
- Rail transit signal UPS backup
Product parameters
- Model:HRL12200W
- Voltage:12 Vdc
- Nominal Capacity:200W @15min-rate
- Watts per Cell:385 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:218 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:20.0 A
- Max. Discharge Current:400 A
- Short Circuit Current:1509 A
- Internal Resistance:5.50 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:17.30 / 38.13 kg / lb.
- Length (L):228.0±2.5 / 8.98±0.10 mm / in
- Width (W):138.4±1.5 / 5.45±0.06 mm / in
- Height (H):206.3±2.5 / 8.12±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HRL12200W belongs to the HRL series, a valve-regulated lead-acid battery with 6V plus 12V top terminal construction, utilizing AGM absorbed glass mat technology to achieve up to 99% gas recombination efficiency, maintenance-free in daily use. This model has a nominal voltage of 12 Vdc, nominal capacity expressed as 200W at the 15-minute rate at 1.67 VPC, 25°C, with cell power of 385 W/cell at the 5-minute rate at 1.67 VPC, 25°C, and 218 W/cell at the 15-minute rate under the same conditions.
In terms of electrical performance, the HRL12200W has a maximum charge current of 20.0 A, maximum discharge current of 400 A, short-circuit current of 1509 A, and internal resistance of 5.50 mΩ. Float charge voltage is 13.5 to 13.8 Vdc/battery (25°C), equalizing charge voltage is 14.4 to 15.0 Vdc/battery (25°C). Self-discharge is controlled below 10% after 90 days, can be stored at 25°C for up to 6 months, requires full charge before use, and if stored above 25°C should be recharged sooner.
Structurally, the battery uses I2 threaded lead alloy terminals, accepts M6 bolts, terminal torque is 51.7±10.3 Kgf·cm or 44.9±9.0 Lbf·in or 5.10±1.0 N·m. The case material is PP (UL 94-HB), with flame-retardant 94-V0 version available upon request. Dimensions are length 228.0±2.5 mm, width 138.4±1.5 mm, height 206.3±2.5 mm, weight 17.30 kg.
The HRL series is positioned as a long-life, high-rate UPS pure lead battery series, aimed at high-power data centers and UPS loads. The HRL12200W has a design life of up to 10 years at 25°C float service, and over 12 years according to Eurobat (20°C) standard, belonging to the very long life classification. Operating temperature: nominal 25°C, discharge range -15°C to 50°C, charge and storage range -15°C to 40°C.
The official application area for this model is data center uninterruptible power supply, suitable for high-rate UPS and float standby power scenarios. The product is manufactured according to IEC 60896-21/22:2004 and is UL1989 recognized (MH14533). The pure lead construction combined with proprietary formulation elements maintains stable performance under float standby and high-rate discharge requirements.