Product Features

  • Valve Regulated Lead Acid (VRLA) Battery
  • Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
  • Pure Lead Construction and Proprietary Elements
  • Designed for High-Rate UPS, Float Service Standby Power Applications
  • Built in Accordance with IEC 60896-21/22:2004 and UL1989 Recognized (MH14533)

Application Scenarios

  • Large data center UPS backup
  • Cloud computing center HVDC backup
  • Financial trading system UPS
  • Telecom hub UPS emergency protection
  • Industrial automation UPS high-power backup
  • Rail transit signal UPS backup

Product parameters

  • Model:HRL12280W
  • Voltage:12 Vdc
  • Nominal Capacity:280W @15min-rate
  • Watts per Cell:506 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:284 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:28.0 A
  • Max. Discharge Current:800 A
  • Short Circuit Current:2576 A
  • Internal Resistance:3.50 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:25.80 / (56.86
  • Length (L):261.0±2.5 / 10.28±0.10 mm / in
  • Width (W):168.5±2.0 / 6.63±0.08 mm / in
  • Height (H):213.5±2.5 / 8.41±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB HRL12280W belongs to the HRL series and is a 12V valve-regulated sealed lead-acid battery using absorbed glass mat (AGM) technology with a gas recombination efficiency of up to 99%, and employs pure lead construction with proprietary elements. The series is officially positioned as a long-life, high-rate UPS pure lead battery series, designed for demanding high-power data center and UPS loads, with the official application area being data center uninterruptible power supplies. In terms of electrical parameters, the HRL12280W has a voltage of 12 Vdc and a nominal capacity (1.67 VPC @25°C) of 280W @15-minute rate. Its 5-minute rate (1.67 VPC @25°C) power is 506 W/cell, and its 15-minute rate (1.67 VPC @25°C) power is 284 W/cell. The battery's maximum charge current is 28.0 A, maximum discharge current is 800 A, short-circuit current is 2576 A, and internal resistance is 3.50 mΩ. Float charge voltage is 13.5 to 13.8 Vdc/battery (25°C), and equalizing charge voltage is 14.4 to 15.0 Vdc/battery (25°C). The battery dimensions are 261.0±2.5 mm length, 168.5±2.0 mm width, and 213.5±2.5 mm height, with a weight of 25.80 lbs (56.86 kg). The terminal type is I2 threaded lead alloy terminal, accepting M6 bolts, with a terminal torque of 51.7±10.3 Kgf∙cm or 44.9±9.0 Lbf∙in or 5.10±1.0 N∙m. The case material is PP (UL 94-HB), and a flame-retardant (94-V0) version is available upon request. In terms of operating environment, the nominal temperature is 25°C, the discharge temperature range is -15°C to 50°C, and the charge and storage temperature range is -15°C to 40°C. The self-discharge rate is less than 10% after 90 days of storage at 25°C, and it can be stored for up to 6 months at 25°C; it must be fully charged before use, and if the storage temperature is above 25°C, it should be charged earlier. The design life is up to 10 years under float service at 25°C, and exceeds 12 years at 20°C per Eurobat standard, belonging to the ultra-long-life class. The battery is maintenance-free, complies with IEC 60896-21/22:2004, and is recognized under UL1989 (MH14533). With high-rate discharge performance and long-life characteristics, the HRL12280W is suitable for high-power standby power scenarios such as data center UPS, providing reliable power assurance in float standby applications.
link
Go to purchase