CSB HRL634W 6V 34W Valve-Regulated Sealed Lead-Acid Battery
The CSB HRL634W is a 6V valve-regulated sealed lead-acid battery in the HRL series, featuring AGM technology and pure lead construction with a 15-minute rate nominal capacity of 34W, suitable for high-rate float standby power applications such as data center UPS.
Taobao store
WeChat procurement
Product Features
- Valve Regulated Lead Acid (VRLA) Battery
- Maintenance-Free, Absorbent Glass Mat (AGM) Technology for Efficient Gas Recombination of up to 99%
- Pure Lead Construction and Proprietary Elements
- Designed for High-Rate UPS, Float Service Standby Power Applications
- Built in Accordance with IEC 61056-1/2:2012 and UL1989 Recognized (MH14533)
Application Scenarios
- Large data center UPS backup
- Cloud computing center HVDC backup
- Financial trading system UPS
- Telecom hub UPS emergency protection
- Industrial automation UPS high-power backup
- Rail transit signal UPS backup
Product parameters
- Model:HRL634W
- Voltage:6 Vdc
- Nominal Capacity:34W @15min-rate
- Watts per Cell:36.33 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:18.17 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:3.40 A
- Max. Discharge Current:130 A
- Short Circuit Current:380 A
- Internal Resistance:8.30 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.32 / 2.91 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):34.0±1.0 / 1.34±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 8 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
- Float Charging Voltage:6.75 - 6.90 Vdc/battery
- Equalizing Charging Voltage:7.20 - 7.50 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The CSB HRL634W belongs to the HRL series, with product types being 6V and 12V top terminal VRLA-AGM batteries, and its official application area is data center uninterruptible power supplies. This series is positioned as a long-life, high-rate UPS pure lead battery series, designed for high-power data centers and UPS loads. The battery adopts a valve-regulated sealed lead-acid structure and absorbed glass mat technology, with gas recombination efficiency of up to 99%, requires no maintenance, and is manufactured with pure lead construction and a proprietary element formula, suitable for high-rate UPS float standby power applications.
In terms of electrical parameters, the HRL634W has a voltage of 6 Vdc, and its nominal capacity is 34W at the 15-minute rate under 1.67 VPC at 25°C. The per-cell power at 30 seconds, 1.67 VPC, 25°C is not provided in the data; at 5 minutes, 1.67 VPC, 25°C it is 36.33 W/cell, and at 15 minutes, 1.67 VPC, 25°C it is 18.17 W/cell. The maximum charging current is 3.40 A, the maximum discharge current is 130 A, the short-circuit current is 380 A, and the internal resistance is 8.30 mΩ. The float charge voltage is 6.75 to 6.90 Vdc/battery (25°C), and the equalizing charge voltage is 7.20 to 7.50 Vdc/battery (25°C).
In terms of construction and dimensions, the HRL634W uses an F2 terminal, i.e., Faston Tab 250. The case material is ABS (UL 94-HB), and a flame-retardant 94-V0 version can be provided upon request. The battery weight is 1.32 kg, i.e., 2.91 lb; the length is 150.9±2.0 mm, i.e., 5.94±0.08 in; the width is 34.0±1.0 mm, i.e., 1.34±0.04 in; and the height is 98.6±1.0 mm, i.e., 3.88±0.04 in.
In terms of environment and life, the design life is up to 8 years under 25°C float standby conditions, and 10 to 12 years for Eurobat (20°C) standard commercial use. The nominal operating temperature is 25°C (77°F), discharge is -15°C to 50°C (5°F to 122°F), and charging and storage are -15°C to 40°C (5°F to 104°F). Self-discharge is less than 10% after 90 days, and it can be stored for up to 6 months at 25°C (77°F); it must be fully charged before use, and if the storage temperature is above 25°C (77°F), it should be charged earlier.
The product is manufactured in accordance with IEC 61056-1/2:2012 and is recognized under UL1989 (MH14533). These features make the HRL634W suitable for applications such as data center UPS that require high-rate discharge and float standby, allowing it to deliver its design and performance at 25°C.